Making energy storage HMA compliance possible | Gas detection requirements and application practices for Singapore Fire Code energy storage systems
News2026-11-04
From the revision of fire safety regulations in 2026, continuous monitoring of combustible gas concentration, to low concentration warning, ventilation linkage, and full lifecycle reliability
With the development of large-scale energy storage and industrial energy storage systems towards higher capacity, higher energy density, and more compact structures, the accumulation of combustible gases and explosion risks caused by thermal runaway of lithium-ion batteries are becoming an important issue in global energy storage safety management.
Singapore is accelerating the construction of energy storage infrastructure. According to the development plan released by the Energy Market Authority (EMA) of Singapore in October 2026, approximately 350 MWh of energy storage capacity has been deployed nationwide, with plans to increase it to over 1 GWh by 2030. Among them, Sembcorp's energy storage project located on Jurong Island has been expanded to 326 MWh, becoming an important representative of large-scale energy storage deployment in Singapore.
As the scale of energy storage deployment expands, how to identify risks in the early stages of abnormal battery development and reduce thermal runaway hazards through gas detection, ventilation linkage, and safety control has become an engineering problem that energy storage equipment manufacturers, system integrators, and operators need to jointly solve.
The Singapore Civil Defense Force (SCDF) continues to revise Section 10.3 of Fire Code 2023 (Energy Storage Systems). Among them, the revised installation terms for above ground energy storage, which will be released on September 1, 2025 and take effect on March 1, 2026, further clarify the requirements for continuous monitoring of combustible gases, 25% LEL concentration control, mechanical smoke exhaust, and explosion risk protection.
Source: https://www.scdf.gov.sg/docs/default-source/fire-safety-docs/firecode-2023-111220241013.pdf?sfvrsn=b3dc3c15_3
This change reflects the important development direction of energy storage fire safety management: based on fire separation and fire protection, further strengthening the identification of thermal runaway gas risks, proactive control, and verification of the effectiveness of safety measures.
Fire Code Continues Revision: Energy Storage Safety Management Transitions from Passive Protection to Active Risk Control
Article 10.3 of the Singapore Fire Code is not an independent regulation added in 2026, but a continuously revised energy storage safety technical requirement under the 2023 version of the fire safety code framework. Its development process reflects the trend of gradually refining energy storage risk management.
2023 edition: Establishing a Fire Safety Management Framework for Energy Storage Systems
Standardize the requirements for the applicable capacity, installation location, fire separation, energy storage capacity limitation, fire protection, and emergency isolation of energy storage systems, providing a basic basis for the fire protection design of energy storage facilities.
Revised in 2025: Further refine safety requirements for underground energy storage
Standardize the establishment of classification management requirements for underground energy storage facilities, clarify the requirements for combustible gas detection, 25% LEL concentration control, mechanical ventilation, fire monitoring, and hazard mitigation analysis (HMA) for specific underground energy storage facilities. Among them, for large underground containerized energy storage facilities, the specifications require safety design and approval in combination with UL 9540A testing and NFPA 855 HMA.
Revision effective March 2026: Further strengthen gas risk management in above ground energy storage battery rooms
SCDF has revised Article 10.3.1 to clarify the requirements for dedicated combustible gas detection, continuous monitoring, mechanical smoke exhaust, explosion protection, BMS, and emergency isolation applicable to above ground energy storage battery rooms.
This means that energy storage fire protection design no longer only focuses on control measures after a fire occurs, but also requires reliable gas monitoring and safety linkage to reduce the possibility of combustible gas accumulation forming hazardous environments.
Summary of Version Changes for Singapore Fire Code Energy Storage System Safety Requirements
Clear gas detection targets: extending from fire detection to risk control of combustible gas accumulation
When internal faults or thermal runaway occur in lithium-ion batteries, combustible gases such as hydrogen (H ₂) and carbon monoxide (CO) may be released. Some combustible gases accumulate in energy storage cabinets, containers, or battery rooms, which may form a mixed atmosphere with combustion or explosion hazards.
Article 10.3.1 (f) of the Singapore Fire Code specifies the requirement for a Dedicated Flammable Gas Detection System for applicable above ground energy storage battery rooms. The system needs to continuously monitor the concentration of combustible gases and control the highest combustible gas concentration below 25% of the lower explosive limit (LEL) by activating the smoke exhaust system.
At the same time, the applicable energy storage battery room should also be equipped with a smoke exhaust and ventilation capacity of at least 9 times per hour; If the most unfavorable operating conditions require a higher air exchange rate, the design should be based on the corresponding conditions. For specific underground containerized energy storage facilities, Article 10.3.3 further requires the design of a dedicated mechanical ventilation system based on the most unfavorable operating conditions determined by UL 9540A testing, and linked with combustible gas detection.
Gas detection not only requires timely detection of anomalies, but also must be able to support effective ventilation control and explosion risk mitigation.
25% LEL concentration control: Low concentration detection to buy time for safe response
For energy storage systems, controlling the concentration of combustible gases is an important goal of safety management, but 25% LEL cannot be directly understood as the alarm set value that all detectors must adopt. Taking hydrogen as an example, its typical lower explosive limit is about 4% vol, which is 40000 ppm.
Hydrogen concentration to LEL ratio
Gas is released from the inside of the battery, diffuses to the detector, and then the control system completes the judgment and executes ventilation or other safety measures, requiring a certain response time. Therefore, using low concentration hydrogen gas detection in validated application scenarios can buy more time for anomaly identification, risk verification, and safety control.
The low concentration detection capability cannot be measured solely by display resolution, but also requires evaluation of measurement errors, zero drift, temperature and humidity effects, background interference, and alarm repeatability. The value of low concentration detection is not only to detect gases earlier, but also to enable safety measures to be activated in a timely manner before risks further develop.
Representative point layout and ventilation linkage: from detection signals to actual risk control
The Singapore Fire Code links gas detection and ventilation systems, providing more complete engineering requirements for the selection, placement, and control logic of detectors for energy storage facilities. For large container energy storage, industrial and commercial energy storage cabinets, and applicable energy storage battery rooms, the number and installation location of detectors should be determined based on the battery exhaust path, cabin structure, equipment barriers, and ventilation conditions.
Gas release and diffusion path: Confirm whether abnormal gases can reach the detection location in a sufficiently short time.
• Detection coverage under different ventilation conditions: Evaluate the impact of normal ventilation, ventilation start-up, and ventilation failure on gas concentration distribution.
Response time for alarm and safety linkage: Confirm that the complete response chain composed of sensors, controllers, communication, and actuators can meet the safety design objectives.
• System Failure and Continuous Monitoring Capability: Clarify monitoring strategies for detector failures, communication interruptions, equipment maintenance, and safety system shutdowns.
For complex energy storage compartments, it is recommended to confirm the gas detection coverage effect through representative release tests, airflow analysis, or validated calculation methods. Merely installing detectors at the top based on low hydrogen density does not guarantee optimal detection performance in all application scenarios.
Environmental adaptability: Ensure detection reliability before and after long-term operation
Energy storage gas detectors require long-term operation in complex environments. Especially in high-temperature areas, energy storage cabinets and containers may experience high temperatures during transportation, storage, installation, and waiting for acceptance, while air conditioning or auxiliary temperature control systems may not have been activated at this time. At the same time, sealants, coatings, cables, and other polymer materials may release substances such as siloxanes and VOCs, causing interference or pollution to some gas sensing technologies.
• Performance retention ability after high temperature exposure: Evaluate the zero point, sensitivity, and alarm performance during high temperature operation, non powered high temperature storage, and recovery to normal temperature.
Stability after exposure to pollutants: Evaluate the effects of siloxanes, solvents, VOCs, and other pollutants on sensing elements, filter materials, and compensation elements.
Continuous effectiveness during long-term operation: Incorporate drift, cross interference, maintenance cycle, and end-of-life criteria into product reliability verification.
The above content belongs to engineering suggestions for implementing on-site reliability, and is not a sensor testing project uniformly specified by SCDF.
From gas detection to HMA: enabling the effectiveness of safety measures to be verified
The Singapore Fire Code references UL 9540A testing and NFPA 855 Hazard Mitigation Analysis (HMA) under specific energy storage installation conditions, and proposes NFPA 68 or NFPA 69 requirements for explosion protection. This means that energy storage safety measures need to be determined based on actual hazardous scenarios and proven effective through analysis and verification.
Whether the detection target, measurement range, and alarm threshold match the dangerous scene;
Can the detector placement represent the actual risk of gas release and accumulation;
Can gas detection, alarm, and ventilation linkage be executed according to the design logic;
Can BMS and other security control measures take action under predetermined conditions;
Whether equipment failures, communication interruptions, and maintenance status are properly managed;
Can the necessary gas response still be maintained after long-term operation
Pu Sheng Sensing is a gas sensing solution specifically designed for energy storage systems and AI data center lithium battery scenarios
As an industry leader in the research and manufacturing of advanced gas sensors, Pusheng Sensing continues to promote technological breakthroughs and international compliance processes in the field of energy storage applications, starting from complex on-site environments.
The company's series of carbon monoxide and hydrogen sensors have become the world's first products to achieve UL silicon poisoning resistance and 85 ° C high temperature reliability certification. The working temperature range of the product covers -40 ℃ to 105 ℃, making it a benchmark in the industry for environmental adaptability, long-term stability, resistance to silicon poisoning, and reliability. It has been widely used in energy storage system safety monitoring, AIDC infrastructure, and new energy related scenarios.
picture
Advanced gas sensing solutions include:
Low concentration and multi-stage hydrogen detection and system linkage
Support 500 ppm low concentration H ₂ warning, as well as multi-level concentration monitoring such as 4000 ppm (10% LEL) and 10000 ppm (25% LEL), providing energy storage systems with graded monitoring capabilities from early anomaly identification to combustible gas risk control.
Low concentration and multi-stage carbon monoxide detection and system linkage
Support multi-level CO concentration detection of 10 ppm, 20 ppm, 120 ppm, etc., providing technical support for battery abnormal exhaust identification, concentration trend monitoring, and graded alarm.
Anti pollution and anti silicon poisoning design
Optimize the anti pollution performance of sensors and enhance measurement stability in complex environments to address the potential presence of siloxanes, VOCs, and other volatile pollutants within energy storage systems.
Wide temperature range and high temperature reliability
Improve the high temperature tolerance and performance maintenance level of sensors in response to temperature changes during transportation, installation, commissioning, and normal operation of energy storage cabinets and containers.
Long lifespan and sustained reliability
By optimizing core materials, sensor structures, and manufacturing processes, long-term measurement stability is improved, and risks of drift, frequent maintenance, and early replacement are reduced.
The measurement range, working temperature, lifespan, and certification scope of specific product models shall be subject to the corresponding product technical documents and test reports.
Reliable gas sensing to support more effective energy storage safety decisions
The continuous revision of Singapore's Fire Code reflects the trend of energy storage fire safety management moving from traditional fire protection to further development of combustible gas risk identification, active control, and system effectiveness verification.
For energy storage manufacturers, system integrators, and operators, regulatory compliance is only the foundation of safety design. How to maintain the accuracy, stability, and sustained effectiveness of gas detection in complex environments will directly affect the actual reliability of the safety protection system.
ProSense not only focuses on the initial performance of gas sensors, but also emphasizes their anti-interference ability, environmental adaptability, and long-term reliability in real energy storage and AI data center lithium battery application environments, helping customers improve the efficiency of thermal runaway risk identification and overall safety assurance level.
Identify risks earlier and make security measures more effective.
ProSense| Making Energy Storage HMA Compliance Possible
About ProSense
ProSense is a high-tech enterprise dedicated to the research and manufacturing of advanced gas sensors, committed to providing high-performance and high reliability sensing solutions for global customers. The company continues to invest in core technology research and development, overcome key pain points in the industry, and continuously lead the development direction of gas sensing technology. With innovative products and excellent quality, ProSense is gradually growing into an important promoter and leader in the global gas safety monitoring field.
ProSense adheres to the full stack self-developed technology route, and has established a kilogram level gas sensor catalyst research and development base and an automated production aging calibration system for millions of gas sensors per year. Its product line covers the fields of toxic and harmful, flammable and explosive, and environmental gas detection; ProSense's multiple innovative products have become core sensing components in vertical fields such as smart firefighting, industrial testing, and energy storage safety.