Enabling HMA | NFCC UK Fire Rescue Agency Guidelines for Gas Detection Requirements and Application Practices in Energy Storage Systems

News2026-11-16
Promote the transformation of energy storage risk assessment into verifiable safety measures through early gas warning, continuous concentration monitoring, and safety linkage

How to configure gas detection in energy storage systems and how the detection results support protective actions are important issues in energy storage safety design. The new version of the UK National Fire Control Commission (NFCC)'s "Planning for Grid Level Energy Storage Systems - Guidelines for Fire Rescue Agencies" integrates detection monitoring with explosion control, providing reference for project design.

Source:  https://nfcc.org.uk/our-services/building-safety/grid-scale-energy-storage-system-planning-guidance-for-fire-and-rescue-services/

Clarify the scope of application and usage of the guidelines

This guide is mainly aimed at outdoor lithium energy storage systems with a capacity of not less than 1 MWh, providing reference for UK fire and rescue agencies to participate in project planning. Its suggestion should be used in conjunction with the on-site situation and should not be mechanically imposed as a unified mandatory requirement by local planning agencies.

Therefore, the starting point of the application guide is to clarify project risks and protection objectives, and then coordinate specific plans with local fire rescue agencies. The technical documents should specify the purpose and basis of the measures adopted, in order to facilitate the assessment of their applicability by all parties.

Early identification requires the cooperation of multiple monitoring methods

Section 8 includes early battery fault identification, BMS temperature monitoring, and early exhaust detection in the discussion, and reminds that it is not enough to rely solely on exhaust detection to predict or prevent thermal events.

The application meaning of this suggestion is that gas signals should be used in conjunction with other operational information. When designing, it is necessary to specify what anomalies are identified by different monitoring methods, and how this information supports judgment and disposal, in order to avoid assigning tasks beyond the capabilities of a single detection channel.

Continuous monitoring should be linked to alarm shutdown and exhaust ventilation

Section 8 suggests implementing continuous monitoring of combustible gases in energy storage cabinets or compartments, and linking gas detection and alarm, energy storage system shutdown, and adequate ventilation.

Therefore, the selection of detection equipment needs to be synchronized with the control design. The project should be able to clearly explain where the alarm signal is transmitted, which system performs shutdown and exhaust, and how to confirm that the relevant actions have been completed.

The device has an alarm interface, which is just one of the conditions for achieving linkage. Engineering verification also requires checking whether the signal transmission, control logic, and execution equipment are effectively connected.

Distribution should serve timely and effective response

The guidelines require consideration of target gas and equipment response time in point deployment, and provide examples of H ₂, CO, and other volatile organic compounds as monitoring objects.

The evaluation focus of point layout design should be whether anomalies can be identified within the required time to support effective response, rather than just the number of detectors or whether the installation location is convenient for construction.

Correctly understand the exhaust control target for combustible gases below 25% LEL

Section 10 proposes that exhaust systems used to prevent explosions should maintain environmental concentrations below 25% LEL.

It is necessary to distinguish between the exhaust control target and the alarm set value here. 25% LEL cannot be directly used as the unified alarm threshold based on this; The design of detection and control also needs to consider the time required for protective actions to take effect. Taking hydrogen as an example, its typical lower explosive limit is about 4% vol, which is 40000 ppm.

Hydrogen concentration to LEL ratio

Gas is released from the inside of the battery, diffuses to the detector, and then the control system completes the judgment and executes ventilation or other safety measures, requiring a certain response time. Therefore, using low concentration hydrogen gas detection in validated application scenarios can buy more time for anomaly identification, risk verification, and safety control.

The low concentration detection capability cannot be measured solely by display resolution, but also requires evaluation of measurement errors, zero drift, temperature and humidity effects, background interference, and alarm repeatability. The value of low concentration detection is not only to detect gases earlier, but also to enable safety measures to be activated in a timely manner before risks further develop.

In terms of design basis, Section 10 of NFCC lists relevant British standards, as well as NFPA 68 "Explosion Relief Protection Standard" and NFPA 69 "Explosion Prevention System Standard" that can serve as equivalent references. The two standards correspond to pressure relief protection and explosion prevention respectively, providing reference for the design and applicability demonstration of the selected explosion-proof measures.

This connection indicates that gas detection should be evaluated together with specific explosion-proof strategies. The detector's ability to sound an alarm does not necessarily mean that the exhaust or pressure relief plan has achieved the design goals; The project still needs to provide corresponding design basis and verification evidence in conjunction with the selected measures.

For emergency ventilation power supply, NFCC further refers to the guidance content of Appendix G.1.4.3.3 of NFPA 855:2023, reminding not to cut off the power supply of the ventilation system that undertakes explosion risk mitigation function during the development of the accident.


ProSense is a gas sensing solution specifically designed for energy storage systems and AI data center lithium battery scenarios

As an industry leader in the research and manufacturing of advanced gas sensors, ProSense continues to promote technological breakthroughs and international compliance processes in the field of energy storage applications, starting from complex on-site environments.

The company's series of carbon monoxide and hydrogen sensors have become the world's first products to achieve UL silicon poisoning resistance and 85 ° C high temperature reliability certification. The working temperature range of the product covers -40 ℃ to 105 ℃, making it a benchmark in the industry for environmental adaptability, long-term stability, resistance to silicon poisoning, and reliability. It has been widely used in energy storage system safety monitoring, AIDC infrastructure, and new energy related scenarios.

Advanced gas sensing solutions include:

Low concentration and multi-stage hydrogen detection and system linkage

Support 500 ppm low concentration H ₂ warning, as well as multi-level concentration monitoring such as 4000 ppm (10% LEL) and 10000 ppm (25% LEL), providing energy storage systems with graded monitoring capabilities from early anomaly identification to combustible gas risk control.

Low concentration and multi-stage carbon monoxide detection and system linkage

Support multi-level CO concentration detection of 10 ppm, 20 ppm, 120 ppm, etc., providing technical support for battery abnormal exhaust identification, concentration trend monitoring, and graded alarm.

Anti pollution and anti silicon poisoning design

Optimize the anti pollution performance of sensors and enhance measurement stability in complex environments to address the potential presence of siloxanes, VOCs, and other volatile pollutants within energy storage systems.

Wide temperature range and high temperature reliability

Improve the high temperature tolerance and performance maintenance level of sensors in response to temperature changes during transportation, installation, commissioning, and normal operation of energy storage cabinets and containers.

Long lifespan and sustained reliability

By optimizing core materials, sensor structures, and manufacturing processes, long-term measurement stability is improved, and risks of drift, frequent maintenance, and early replacement are reduced.

The measurement range, working temperature, lifespan, and certification scope of specific product models shall be subject to the corresponding product technical documents and test reports.


Reliable gas sensing to support more effective energy storage safety decisions

For energy storage manufacturers, system integrators, and operators, regulatory compliance is only the foundation of safety design. How to maintain the accuracy, stability, and sustained effectiveness of gas detection in complex environments will directly affect the actual reliability of the safety protection system.

ProSense not only focuses on the initial performance of gas sensors, but also emphasizes their anti-interference ability, environmental adaptability, and long-term reliability in real energy storage and AI data center lithium battery application environments, helping customers improve the efficiency of thermal runaway risk identification and overall safety assurance level.

Identify risks earlier and make security measures more effective.

ProSense | Making Energy Storage HMA Compliance Possible


About ProSense

ProSense is a high-tech enterprise dedicated to the research and manufacturing of advanced gas sensors, committed to providing high-performance and high reliability sensing solutions for global customers. The company continues to invest in core technology research and development, overcome key pain points in the industry, and continuously lead the development direction of gas sensing technology. With innovative products and excellent quality, ProSense is gradually growing into an important promoter and leader in the global gas safety monitoring field.
ProSense adheres to the full stack self-developed technology route, and has established a kilogram level gas sensor catalyst research and development base and an automated production aging calibration system for millions of gas sensors per year. Its product line covers the fields of toxic and harmful, flammable and explosive, and environmental gas detection; ProSense multiple innovative products have become core sensing components in vertical fields such as smart firefighting, industrial testing, and energy storage safety.
Contact Us
Contact Us
Online Service
Provide comprehensive customer service through real-time communication
Consult Now
Official Flagship Store
Build a first-class gas sensing solution provider
Wechat Official Account
Follow the official WeChat QR code of ProSense
View QR Code